450

DPS 450 SP

Sound Proof 450 kVA Generator Set

  • Cooling : Oil
  • Fuel :Gasoil
Product composition
EngineDEUTZ
AlternatorMecc Alte
CowlingInsonorisé
Control boxStandard
General data
Power (PRP)450 KVA
Power (PRP)360 KW
Power (LTP)495 KVA
Power (LTP)396 KW
Amp648 A
Regime 1500 RPM
Frequency50 Hz
Tension230/400 V
Power factor0.8 Cos Phi
Fuel Data
KindGasoil
Tank capacity1000 L
Autonomy at 75% load13 H
Fuel consumption (Diesel at 850g/l)
25 % load216 g/kWh - 26.2 l/h
50 % load203 g/kWh - 49.3 l/h
75 % load203 g/kWh - 74.0 l/h
100 % load208 g/kWh - 101.0 l/h
PRP (Prime Running Power)
Applicable to power a variable electrical load for an unlimited number of hours. Main Power (PRP) conforms to ISO 8528. Ten percent overload capability is available, conforming to ISO 3046, AS
LTP (Limited Time Power)
Applicable to power a constant electrical load for a limited number of hours. Limited Time Operating Power (LTP) conforms to ISO 8528.

Order now

Phone :