500

DPS 500 SP

Sound Proof 500 kVA Generator Set

  • Cooling : Oil
  • Fuel :Gasoil
Product composition
EngineDEUTZ
AlternatorMecc Alte
CowlingInsonorisé
Control boxStandard
General data
Power (PRP)500 KVA
Power (PRP)400 KW
Power (LTP)550 KVA
Power (LTP)440 KW
Amp720 A
Regime 1500 RPM
Frequency50 Hz
Tension230/400 V
Power factor0.8 Cos Phi
Fuel Data
KindGasoil
Tank capacity1000 L
Autonomy at 75% load12 H
Fuel consumption (Diesel at 850g/l)
25 % load216 g/kWh - 28.4 l/h
50 % load203 g/kWh - 53.5 l/h
75 % load203 g/kWh - 80.2 l/h
100 % load208 g/kWh - 109.6 l/h
PRP (Prime Running Power)
Applicable to power a variable electrical load for an unlimited number of hours. Main Power (PRP) conforms to ISO 8528. Ten percent overload capability is available, conforming to ISO 3046, AS
LTP (Limited Time Power)
Applicable to power a constant electrical load for a limited number of hours. Limited Time Operating Power (LTP) conforms to ISO 8528.